Photohelic® Switch/Gages in Flame-Proof Enclosures
Approved Photohelic® Switch/Gages with 120, 240 or 24 VAC Power are available in aluminum with glass window, allowing for viewing of set point needles and process pressure.
 
Features
	- 
	3-in-1 ATEX approved instrument allows the reduction of several instruments with one product, saving inventory, installation time and money 
- 
	Flame-proof ATEX enclosure with optional glass window and aluminum housing protects the device in hazardous areas while giving local visibility to process pressure and set point status 
Product Applications
Specifications
	- 
	Service: Air and non-combustible, compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Accuracy: ±2% of FS at 70°F (21.1°C); ±3% on -0 and ±4% on -00 models. 
- 
	Pressure Limits: -20 in Hg to 25 psig (-0.677 to 1.72 bar). MP option; 35 psig (2.41 bar), HP option; 80 psig (5.52 bar). 
- 
	Temperature Limits: 20 to 120°F (-6.67 to 48.9°C) LT low temperature option to -20°F available; (Note: Product temperature limits differ from case). 
- 
	Dial Size: 4" (101.6 mm). 
- 
	Mounting Orientation: Diaphragm in vertical position. 
- 
	Set Point Adjustment: Adjustable knobs on Photohelic® gage face behind enclosure cover. Follow instructions and safety warnings to open cover. 
SWITCH SPECIFICATIONS:
	- 
	Switch Type: Each setpoint has 2 Form C relays (DPDT). 
- 
	Repeatability: ±1% of FS. 
- 
	Electrical Rating: 10 A @ 120 VAC, 6 A @ 240 VAC, 60 Hz res. 10 A @ 28 VDC. 
- 
	Electrical Wiring: Screw terminals. 
- 
	Power Requirements: 120 VAC, 50/60 Hz; 240 VAC & 24 VAC power optional. 
- 
	Enclosure Rating: IP66. IP65 with option OPV, overpressure relief valve. 
- 
	Housing material: Aluminum. 
- 
	Finishing: Texture epoxy coat RAL7038. 
- 
	Pressure Connections: 1/8" NPT female brass (SS optional). In presence of acetylene it is necessary to use SS. 
- 
	Electrical Connections: Three 1/2" FNPT. Cable gland not included. 
- 
	Weight: 28.4 lb (12.9 kg). 
- 
	ATEX Certificate: BVI 14ATEX0072. 
- 
	Agency Approvals: ATEX Compliant CE 1370 Ex II 2G Ex d IIC T6 Gb / II 2D Ex tb IIIC T85°C Db, -60°C=Tamb=+60°C IECEx Compliant: Ex d IIC T6 Gb / Ex tb IIIC T85°C Db