Combines Differential Pressure Gage with Low/High Set-Points, Compact Size
Photohelic® Switch/Gage combines functions of a precise, highly repeatable differential pressure switch with a large analog pressure gage. Applications include air conditioning systems and pneumatic conveying.
 
Features
	- 
	Gage reading unaffected by switch operation and will continue to read pressure even during power loss 
- 
	Zero and range adjustments outside of gage means no disassembly in normal service 
- 
	Solid-state design allows for switching in high cycle rate applications without degradation 
Product Applications
	- 
	Pneumatic Conveying 
- 
	Air Conditioning Systems 
- 
	Clean Rooms 
Specifications
GAGE SPECIFICATIONS
	- 
	Service: Air and non-combustible, compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Accuracy: ±2% of FS (3000-0 ±3% of FS). (3000-00 ±4% of FS). 
- 
	Pressure Limit: -20" Hg. to 25 psig (-0.677 bar to 1.72 bar). MP option: 35 psig (2.41 bar), HP option: 80 psig (5.52 bar). 
- 
	Temperature Limits: 20 to 120°F (-6.67 to 48.9°C). 
- 
	Process Connections: 1/8" female NPT (duplicated side and back). 
- 
	Size: 4" (101.6 mm) dial face, 5" (127 mm) OD x 3-1/8" (79.38 mm). 
- 
	Weight: 1.8 Ib (816 g). 
SWITCH SPECIFICATIONS 3000MR
	- 
	Switch Type: Each setpoint has 1 form C relays (SPDT). 
- 
	Relay Contacts: (Resistive load) 1 form C rated 1.0A @ 30 VDC, 0.3A @ 110 VDC or 0.5A @ 125 VAC. Gold over clad silver - suitable for dry circuits. 
- 
	Electrical Connections: 18" (46 cm) cable assembly with 8 conductors. Optional lengths to 100' (30.5 m). 
- 
	Power Requirements: 24 VDC, regulated ±10%. 
- 
	Mounting Orientation: Diaphragm in vertical position. Consult factory for other position orientations. 
- 
	Set Point Adjustment: Adjustable knobs on face. 
- 
	Agency Approvals: CE. 
SWITCH SPECIFICATIONS 3000MRS
	- 
	Switch Type: Each setpoint has a solid state relay. 
- 
	Switching Voltage: 20-280 VAC (47-63 Hz). 
- 
	Switching Current: 1.0 amp (AC) max., 0.01 mA (AC) min., (2) SPST NO. 
- 
	Electrical Connections: 18" (46 cm) cable assembly with 6 conductors, optional lengths to 100' (30.5 m). 
- 
	Power Requirements: 24 VDC, regulated ±10%. 
- 
	Mounting Orientation: Diaphragm in vertical position. Consult factory for other position orientations. 
- 
	Set Point Adjustment: Adjustable knobs on face. 
- 
	Agency Approvals: CE.