24 Volt or Battery Powered. Fits in Magnehelic® Gage Cut-Out
DigiMag® Digital Differential Pressure and Flow Gages monitors the pressure of air and compatible gases. 4-digit LCD can display readings in common English or metric units.
 
Features
	- 
	Field programmed reduces installation time 
- 
	User selectable parameters for pressure, air velocity or flow permits same device for multiple applications 
- 
	Specialized filter set point for alerts when maintenance is due 
- 
	Security levels permit matches the correct access to right skill 
- 
	Power versatility works with 9-24 VDC or 9 V battery allows deployment in a variety of spaces wired or not 
Product Applications
Specifications
	- 
	Service: Air and non-combustible, compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Housing Materials: Glass filled plastic. 
- 
	Accuracy: ±1% FS including linearity, hysteresis and repeatability; ±2% FS for ranges 1" w.c. and below. 
- 
	Temperature Limits: 0 to 140°F (-18 to 60°C). 
- 
	Compensated Temperature Limits: 32 to 122°F (0 to 50°C). 
- 
	Long Term Stability: ±1% FS per year. 
- 
	Thermal Effect: ±0.05% FS/°F typ.; ±0.10% FS/°F typ. for ranges 1" w.c. and below. 
- 
	Display: 4-digit LCD (Digits: 0.60"H x 0.33"W). 
- 
	Display Update: Selectable for 1 second, 10 minutes or update only from button push. 
- 
	Pressure Limits: Normal and bi-directional ranges 5 in w.c. and lower = 2 psi (13.7 kPa); Normal and bi-directional ranges 10 in w.c. and higher = 11 psi (75 kPa). 
- 
	Selectable Engineering Units: in w.c., psi, kPa, Pa, mm w.c., mBar, in Hg, mm Hg, FS (0-100% FS). 
- 
	Power Requirements: 9V battery, included, user replaceable or external power supply 9-24 VDC. 
- 
	Battery Service Life: Battery life depending on the Display Update setting: 150 hours (typical) if Display Update = 1 second; 9 months (typical) if Display Update = 10 minutes; 1.5 years (typical) if Display Update is disabled. Battery may last up to four times longer when using lithium-based battery ULTRALIFE U9VL-J. 
- 
	Current Consumption: 5 mA maximum. 
- 
	Electrical Connections: Removable terminal block for 16 to 26 AWG. 
- 
	Electrical Entry: Cable gland for 0.114 to 0.250" (2.9 to 6.4 mm) diameter cable. 
- 
	Process Connections: 1/8" (3 mm) ID tubing. 
- 
	Enclosure Rating: NEMA 4X (IP66). 
- 
	Weight: 1.18 lb (535 g). 
- 
	Size: 5" (127 mm) OD front face. 
- 
	Agency Approvals: CE.