NEMA 4X Enclosure, Low Differential Set Points
Wet/Wet Differential Pressure Switch for use with most gases and water based solutions. Externally adjustable set point, integral mounting flange and a removable electrical terminal block for quick and easy installation.
 
Features
	- 
	Differential pressure switch that is suitable for most gas and water-based applications allows multiple uses in the most sophisticated designs 
- 
	Weatherproof housing provides protection in the harsh, wet or dirty environments ensuring switch’s long-service life 
- 
	Removable terminal block reduces installation time 
Product Applications
	- 
	Indicating filter condition 
- 
	Proof of flow indicator monitoring 
- 
	Proving flow through a pump 
- 
	Proving flow through a chiller 
- 
	Proving flow through a heat pump or AC unit 
Specifications
	- 
	Service: Compatible gases and liquids. 
- 
	Wetted Materials: Connection: Brass; Diaphragm: Fluoroelastomer. 
- 
	Temperature Limits: 30 to 140°F (-1 to 60°C). 
- 
	Pressure Limits: Maximum static pressure: 200 psig (13.8 bar); maximum differential pressure: 1.25 x model’s highest set point. 
- 
	Enclosure Rating: Weatherproof UL type 4X (IP65). 
- 
	Repeatability: ±2% of full range. 
- 
	Switch Type: SPDT snap switch. 
- 
	Electrical Rating: 5 A @ 125/250 VAC, 5 A res. @ 30 VDC. 
- 
	Electrical Connection: Removable terminal block. 
- 
	Conduit Connection: 0.871" diameter hole for 1/2" conduit fitting. 
- 
	Process Connection: 1/4" NPT female. 
- 
	Mounting Orientation: Ports on horizontal plane, ±10°. 
- 
	Set Point Adjustment: External screw. 
- 
	Housing Materials: Body: Aluminum; Housing: Polycarbonate; Cover: 300 SS. 
- 
	Vibration and Shock: Set point repeats after 2.5 Gs, 5 to 500 Hz. Set point repeats after a 15 Gs, 10 millisecond duration. 
- 
	Humidity Limit: 80% (non-condensing). 
- 
	Pollution Degree: 2. 
- 
	Environment: Intended for indoor and outdoor use. 
- 
	Weight: 1 lb 3 oz (0.54 kg). 
- 
	Agency Approvals: CE, cULus.