±0.25% or ±0.5% FS Accuracy, Ranges from 0 to 25" w.c.
Low Range Differential Pressure Transmitter combine low ranges with stability and reliability. Ultra thin glass clad silicon diaphragm design resists shock and vibration, practically eliminates drift.
 
Features
	- 
	High stability at low pressure ranges provides exceptional accuracy for ensuring tight-control and minimizing costly out of specification conditions 
- 
	Provides sensitivity to pressure changes but resists vibration preventing drift and less accurate readings 
- 
	Stainless steel housing meets standards for lab and clean room applications 
 
Product Applications
Specifications
	- 
	Service: Air and non-conductive, non-corrosive gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Accuracy: ±0.5% or ±0.25% FS. 
- 
	Stability: ±0.5% FS/yr. 
- 
	Temperature Limits: -20 to 160°F (-29 to 71°C), 10 to 95% RH. 
- 
	Pressure Limits: 10 psig (0.69 bar). 
- 
	Compensated Temperature Range: 35 to 135°F (2 to 57°C). 
- 
	Thermal Effects: ±0.015% F.S./°F (zero and span). 
- 
	Power Requirements: 12 to 36 VDC. 
- 
	Output Signal: 4 to 20 mA DC, 2-wire. 
- 
	Zero and Span Adjustments: Externally accessible potentiometers, non-interactive, ±10% F.S. adjustment. 
- 
	Response Time: 250 ms max. 
- 
	Loop Resistance: 0 to 1045 ohms Vmin=12V+[(.22A)(RL)]. 
- 
	Current Consumption: 3.6 mA (min). 
- 
	Electrical Connections: Screw terminals. 
- 
	Process Connections: Barbed stainless steel for 3/16" I.D. tubing. 
- 
	Housing: 300 Series stainless steel (NEMA 2). 
- 
	Weight: 1.04 lb (472 g). 
- 
	Agency Approvals: CE.