Mounts on 35 mm DIN Rail, ±0.25% Full Scale Accuracy
DIN Rail Differential Pressure Transmitter are not intended for re-ranging. Designed to mount on a DIN rail. Versatile circuit design enables operation in 2-wire current loops.
 
Features
	- 
	Simple calibration push-buttons to set zero and span 
- 
	Cost effective and compact device suitable for OEM applications where space, simplicity, and value are key 
Product Applications
	- 
	Air handlers 
- 
	Duct pressure 
- 
	Variable air volume 
- 
	Filter monitoring 
Specifications
	- 
	Service: Air and non-combustible, compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Accuracy: ±0.25 FS @ 77°F (25°C). 
- 
	Thermal Effect: ±0.02% FS/°F (0.036% FS/°C). 
- 
	Stability: ±1% FS/yr. 
- 
	Temperature Limits: 14 to 185°F (-10 to 85°C). 
- 
	Pressure Limits: See chart on catalog page. 
- 
	Power Requirements: 10 to 35 VDC (2-wire); 17 to 36 VDC, or isolated 21.6 to 33 VAC (3-wire). 
- 
	Output Signal: 4 to 20 mA (2-wire); 0 to 10 VDC (3-wire). 
- 
	Zero and Span Adjustments: Push buttons. 
- 
	Loop Resistance: Current output: 0 to 1250 Ω max; Voltage output: Load resistance 1 kΩ min. 
- 
	Current Consumption: 40 mA max. 
- 
	Electrical Connections: Screw-type terminal block. 
- 
	Process Connections: 1/8" female NPT. Accessories included are 2 barbed fittings for 1/8" (3.12 mm) and 3/16" (4.77 mm) ID rubber or vinyl tubing. 
- 
	Mounting Orientation: Vertical, on a 1.378" (35 mm) DIN rail. 
- 
	Weight: 4.8 oz (136 g). 
- 
	Agency Approvals: CE.