Monitors Pressure & Air Velocity
Magnesense® Differential Pressure Transmitter is versatile in measuring pressure and air velocity. Applications include building pressure monitoring, filter condition monitoring, and fan velocity measurement.
 
Features
	- 
	Field selectable English or Metric ranges 
- 
	Field upgradeable LCD display 
- 
	Adjustable damping of output signal (with optional display) 
- 
	Ability to select a square root output for use with pitot tubes and other similar flow sensors 
Product Applications
	- 
	Building pressure monitoring 
- 
	Duct pressure monitoring 
- 
	Fan velocity measurement 
- 
	Zone differential pressure monitoring 
- 
	Filter condition monitoring 
Specifications
	- 
	Service: Air and non-combustible compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Accuracy: ±1% for 0.25" (50 Pa), 0.5" (100 Pa), 2" (500 Pa), 5" (1250 Pa), 10" (2 kPa), 15" (3 kPa), 25" (5 kPa) ±2% for 0.1" (25 Pa), 1" (250 Pa) and all bidirectional ranges. 
- 
	Stability: ±1% FS/year. 
- 
	Temperature Limits: 0 to 150°F (-18 to 66°C). 
- 
	Pressure Limits: 1 psi maximum, operation; 10 psi, burst. 
- 
	Power Requirements: 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire). 
- 
	Output Signals: 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire). 
- 
	Response Time: 300 ms. 
- 
	Zero & Span Adjustments: Digital push button. 
- 
	Loop Resistance: Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 kΩ. 
- 
	Current Consumption: 40 mA max. 
- 
	Display (optional): 4 digit LCD. 
- 
	Electrical Connections: 4-20 mA, 2-wire: European Style Terminal Block for 16 to 26 AWG. 0-10 V, 3-wire: European Style Terminal Block 16 to 22 AWG. 
- 
	Electrical Entry: 1/2" NPS Thread. Accessory: Cable Gland for 5 to 10 mm diameter cable. 
- 
	Process Connection: 3/16" (5 mm) ID tubing. Maximum OD 9 mm. 
- 
	Enclosure Rating: NEMA 4X (IP66). 
- 
	Mounting Orientation: Diaphragm in vertical position. 
- 
	Weight: 8.0 oz (230 g). 
- 
	Agency Approvals: CE.