Selectable Ranges of Uni-Directional or Bi-Directional, Selectable Outputs
Differential Pressure Transmitter measures flow of various liquids and gases, pressure drop across filters, and energy management.
 
Features
	- 
	Versatile device for liquid or gas supports designs requiring more precise measurements in support of application 
- 
	Field selectable port swap eliminates costly re-plumbing if unit is re-installed or replaced 
- 
	Uni-directional and bi-directional pressure selection with configurable output provides a single device that can meet broad application needs without having to specify multiple devices 
- 
	Optional LCD display provides local status to identify operational conditions 
- 
	NEMA 4 rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists 
Product Applications
Specifications
	- 
	Service: Gases or liquids compatible with 17-4 PH stainless steel. 
- 
	Accuracy: All pressure ranges have ±1% full scale accuracy except the lowest selectable range of each unit is ±2% full scale. 
- 
	Stability: ±0.5% per year. 
- 
	Temperature Limits: Compensated temperature range: 32 to 130°F (0 to 54°C); Operating temperature range: -4 to 185°F (-20 to 85°C). 
- 
	Pressure Limits: Max working pressure: WWDP-1: 50 psi; WWDP-2: 100 psi; WWDP-3: 250 psi; Proof pressure: 2.2X of full scale; Burst pressure: 40X of full scale. 
- 
	Thermal Effect: 2% FS/100°F (50°C) includes zero and span. 
- 
	Power Requirements: 12 to 30 VDC/18 to 28 VAC (Reverse Excitation Protected). NOTE: 4 to 20 mA output cannot be powered with AC voltage. 
- 
	Output Signal: Selectable 0 to 5, 0 to 10 and 1 tp 5 VDC; 4 to 20 mA. 
- 
	Zero & Span: Digital "re" zero button (should be used when changing ranges). Span can be adjusted by changing between field selectable ranges. 
- 
	Response Time: 1 to 5 sec (selectable). 
- 
	Loop Resistance: 1000 Ω. 
- 
	Current Consumption: VDC power: 0 to 5, 1 to 5 VDC output 4 mA (typ); 0 to 10 VDC output 5 mA (typ); 4 to 20 mA output 20 mA max. Current consumption will equal the transmitter output in current mode. VAC power: 0 to 5, 1 to 5, 0 to 10 VDC output 40 mA (typ). 
- 
	Electrical Connections: 1/2" conduit. 
- 
	Process Connections: 1/8" female NPT internal. 
- 
	Enclosure Rating: Designed to meet NEMA 4 (IP66). 
- 
	Mounting Orientation: Vertical; mount the pressure ports down (keeps debris from building up inside the pressure port). 
- 
	Weight: 1.5 lb (680.4 g). 
- 
	Agency Approvals: CE.