Thông số kỹ thuật
- Service: Clean air and compatible, non-combustible gases.
- Accuracy: 3% FS Process gas: 32 to 122°F (0 to 50°C); 4% FS Process gas: -40 to 32°F & 122 to 212°F (-40 to 0°C & 50 to 100°C).
- Response Time: Flow: 1.5 s to 95% of final value (output filter set to min.).
- Temperature Limits: Process: -40 to 212°F (-40 to 100°C). Ambient: 32 to 140°F (0 to 60°C).
- Pressure Limit: 100 psi (6.89 bar) maximum.
- Humidity Limit: Non-Condensing.
- Power Requirements: 12 to 35 VDC, 10 to 16 VAC. 1.5 A rating required on supply due to initial power surge drawn by transmitter.
- Output Signal: 4 to 20 mA, isolated 24 V source, 3 or 4-wire connection.
- Output Filter: Selectable 0.5-15 s.
- Loop Resistance: 600 Ω max.
- Current Consumption: 300 mA max.
- Electrical Connections: Screw terminal.
- Mounting Orientation: Unit not position sensitive. Probe must be aligned with airflow.
- Weight: 13.2 oz (374.26 g).
- Cable Length: 6' (1.82 m).
- Probe Length: 12" (30.48 cm) standard.
- Probe Diameter: 5/16" (0.79 cm).
OPTIONAL DISPLAY VERSION:
- Display: 4-1/2 digit 1/2" red LED.
- Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and 15,000 FPM ranges).
- Weight: 13.9 oz (394.16 g).