Input: 0 to 20 mA, 4 to 20 mA, 0 to 5V, or ±10V inputs; A 85-265 VAC or 12/24 VDC.
Input Impedance: 50 to 100 Ω.
Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span.
Power Requirements: 85 to 265 VAC 50/60 Hz, 90 to 265 VDC, 20 W max or 12 to 24 VDC ±10%, 15 W max.
Display: Dual-line 6-digit display, 0.60 in and 0.46 in.
Decimal Points: Five positions, user selectable.
Temperature Limits: Operating: -40 to 149°F (-40 to 65°C); Storage: -40 to 185°F (-40 to 85°C).
Enclosure Rating: NEMA 4X, IP65 front.
Electrical Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Output Signal: 4 to 20 mA.
Power Consumption: 85 to 265 VAC models: 200 mA @ 24 VDC; 12 to 24 VDC models: 100 mA @ 24 VDC; Second supply with output 2 models: 40 mA @ 24 VDC.
Switch Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for inductive loads.
Time Delay: 0 to 999.9 sec, on & off relay time delays; programmable and independent for each relay.
Shipping Weight: 9.5 oz (269 g).
Agency Approvals: CE, RoHS, cUL, UL.
Programming Software: Free, USB based. Resident on meter, nothing to download.