Low Ranges Down to 0.25" w.c. (60 Pa), NEMA 4X Housing
Differential Pressure Transmitters sense low pressure of air and gases, then sends an output signal. All models are factory calibrated to specific ranges as listed in the chart below.
Features
-
NEMA 4X rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists
-
Easy to read LCD display provides immediate local alerts allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
-
Zero and span controls provides easy calibration checks and shorter installation time to get device running and monitoring
-
High precision accuracy at low pressure ranges provides exceptional accuracy for insuring tight-control and minimizing costly out of specification conditions
Product Applications
Specifications
-
Service: Air and non-combustible, compatible gases.
-
Wetted Materials: Consult factory.
-
Accuracy: ±0.50% F.S., display accuracy ±0.5%.
-
Stability: ±1% F.S./yr.
-
Temperature Limits: 0 to 140°F (-17.8 to 60°C).
-
Compensated Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
-
Pressure Limits: See Catalog page.
-
Thermal Effect: ±0.02% F.S./°F (0.036% F.S./°C).
-
Power Requirements: 12 to 30 VDC (2-wire).
-
Output Signal: 4 to 20 mA.
-
Zero and Span Adjustments: Digital, Push Button Adj.
-
Loop Resistance: DC; 0 to 900 Ω maximum.
-
Current Consumption: DC; 38 mA maximum.
-
Electrical Connections: Screw-type terminal block.
-
Process Connections: Barbed, dual size to fit 1/8" and 3/16" (3.12 and 4.76 mm) I.D. rubber or vinyl tubing.
-
Enclosure Rating: NEMA 4X (IP66).
-
Mounting Orientation: Vertical, consult factory for other position orientations.
-
Weight: Without LCD 17 oz (482 g); with LCD 18 oz (510 g).
-
Agency Approvals: CE.