Series MS in Flame-Proof Enclosure
ATEX/IECEx Approved Magnesense® Differential Pressure Transmitter is versatile in monitoring pressure and air velocity in hazardous locations.
 
Features
	- 
	ATEX housing provides all the capabilities and value of the MS2 in a flame & explosion proof enclosure 
- 
	Durable and rugged housing and high-quality components combined provides longservice life and minimized down-time 
- 
	High impact strength and high temperature rated for applications where hazardous environments exist 
Product Applications
	- 
	Monitor pressures in ducts, rooms, or total building pressures 
- 
	Filter monitoring 
- 
	Local indication of clean room pressures with process signal sent to control room 
- 
	Hazardous area pressure measurement and transmitter 
Specifications
	- 
	Service: Air and non-combustible, compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Accuracy: MS-X21: 0.5 in w.c. & 0.25 in w.c.: ±1%; 0.1 in w.c.: ±2%; 100 Pa & 50 Pa: ±1%; 25 Pa: ±2%. MS-X11: 5 in w.c. & 2 in w.c.: ±1%; 1 in w.c.: ±2%; 1250 Pa & 500 Pa: ±1%; 250 Pa: ±2% (@ standard conditions). 
- 
	Stability: ±1% FS/year. 
- 
	Temperature Limits: 0 to 150°F (-18 to 66°C); (Note: Product temperature limits differ from case). 
- 
	Pressure Limits: 1 psi maximum, operation; 10 psi, burst. 
- 
	Power Requirements: 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire). 
- 
	Output Signals: 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire). 
- 
	Response Time: Field adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds. 
- 
	Zero & Span Adjustments: Digital push button. In safe zone only. 
- 
	Loop Resistance: Current output: 0 to 1250 ohm max.; Voltage output: min. load resistance 1 k ohm. 
- 
	Current Consumption: 40 mA max. Display: 4 digit LCD. 
- 
	Display: 4 digit LCD. 
- 
	Electrical Wiring: 4 to 20 mA, 2-wire: European style terminal block for 16 to 26 AWG. 0 to 10 V, 3-wire: European style terminal block 16 to 22 AWG. 
- 
	Mounting Orientation: Diaphragm in vertical position. 
- 
	Enclosure Rating: 4X IP66, IP65 with option OPV overpressure relief valve. 
- 
	Housing Material: Aluminum. 
- 
	Finishing: Texture epoxy coat RAL7038. 
- 
	Pressure Connections: 1/8" NPT female brass (SS optional). In presence of acetylene it is necessary to use SS. 
- 
	Electrical Connections: Two 1/2" FNPT. Cable gland not included. 
- 
	Weight: 11 lb (5 kg). 
- 
	ATEX Certificate: BVI 14ATEX0072. 
- 
	Agency Approvals: ATEX Compliant CE 1370 Ex II 2G Ex d IIC T6 Gb / II 2D Ex tb IIIC T85°C Db, -60°C=Tamb=+60°C IECEx Compliant: Ex d IIC T6 Gb / Ex tb IIIC T85°C Db