For Sensing Low Pressure Using High Accuracy
Room Status Monitor is designed for critical differential pressure applications that need pressure monitoring and alarming. Applications include manufacturing, clean rooms, research labs, and pharmaceutical.
Features
-
Accurately monitor protective environments for negative or positive pressure ensuring safety and reducing risk of catastrophic events
-
Audible and visual alarm provides immediate local alerts allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
-
Password protected set up menu helps to insure no errors by untrained personnel
-
Optional BACnet communication from devices provides integration into building control system for automated control and centralized monitoring and alarming
Product Applications
-
Hospital Isolation Wards
-
Pharmaceutical
-
Manufacturing
-
Clean Rooms
-
Research Labs
-
Animal Facilities
Specifications
-
Service: Air or nonconductive, nonexplosive gases.
-
Accuracy: ±0.5% FS.
-
Temperature Limits: 32 to 120°F (0 to 50°C).
-
Humidity Limits: 5 to 95% relative humidity (non-condensing).
-
Thermal Effects: ±0.03% FS/ °F (± 0.05% FS/ °C).
-
Pressure Limits: ±15 in w.c. (±3.7 kPa).
-
Supply Voltage: Order Code A (24 VAC): 18-32 VAC, 50-60 Hz. Order Code B (120 VAC): 85-265 VAC, 50-60 Hz. Main supply voltage fluctuations up to 10%.
-
Power Consumption (voltage output): 5 W.
-
Output Signal: Selectable 4-20 mA (2-wire), 0-5 VDC (3-wire), or 0-10 VDC (3-wire).
-
Switch Type:SPST.
-
Loop Resistance (4-20 mA output): 0-510 Ω.
-
Electrical Connection: Removable terminal block.
-
Process Connections: Barbed fittings for 3/16" ID tubing.
-
Enclosure Rating: NEMA 1 (IP20) rated for indoor applications.
-
Housing: Fire retardant plastic.
-
Mounting: Mount to standard double gang metal electrical box using 4x4" plaster ring adapter.
-
Dimensions: 8" H x 5.4" W x 1.8" D (20.3 H x 13.7 W x 4.1 D cm).
-
Weight: 1.5 lb (680 g).
-
Communications: BACnet MSTP ASC optional. Agency Approval: CE, CSA (RSM only).