Specifications
-
Service: Air and non-combustible gases.
-
Wetted Materials: Ranges 5 in w.c. and Greater: glass, PVC, silicon, alumina ceramic, epoxy, RTV, gold, aluminum, stainless steel and nickel; Ranges 1 in w.c. and Lower: stainless steel, silicone, gold, ceramic.
-
Housing Materials: Aluminum, glass.
-
Accuracy: ±0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up).
-
Stability: < ±1% per year.
-
Pressure Limits: Ranges ≤ 2.5 in w.c.: 2 psi; 5 in w.c.: 5 psi; 10 in w.c.: 5 psi; 25 in w.c.: 5 psi; 50 in w.c.: 5 psi; 100 in w.c.: 9 psi.
-
Temperature Limits: 32 to 140°F (0 to 60°C).
-
Compensated Temperature Limits: 32 to 140°F (0 to 60°C).
-
Thermal Effects: 0.020%/°F (0.036/°C) from 77°F (25°C).
-
Power Requirements: 10 to 35 VDC.
-
Output Signal: 4 to 20 mA DC.
-
Zero & Span Adjustments: Accessible via menus.
-
Response Time: 250 ms (damping set to 1).
-
Display: 4 digit LCD 0.6" height.
-
Electrical Connections: M-12 4 PIN Connector.
-
Process Connections: 1/8" female NPT.
-
Enclosure Rating: Designed to meet NEMA 4X (IP66).
-
Mounting Orientation: Mount unit in vertical plane.
-
Weight: 2 lb 10 oz (1.19 kg).
-
Agency Approvals: CE: CENELEC EN 61326/55024: 2003; IEC 61000-4-2/3/4/6: 2001/2006/2004/2005; CENELEC EN 55011: 2006; 2004/108/EC EMC Directive; FM Intrinsically Safe CLI Div I GR: A, B, C, D; CLII Div I GR: E, F, G; CLIII Div I.